Battery cables
Heat resistant/HOFR PVC Insulated Extra Flexible Battery Cables
Request Price Download BrochureAt Vipul Copper we expertise in manufacturing PVC insulated battery cables and Rubber insulated battery cables. Available in two different styles North American and European with 6AWG to 4/0AWG and 10sqmm to 240sqmm sizes respectively. Certified by international quality standards our battery cables are tested under temperature from -40c – 105c and are resistant to oil, acid, fuel, cooling agent, abrasion and more.

Application
- PVC battery cables are largely used in place of function with water, oil and petrol, with quality standards IS-8130, BS-6360, IEC 228 & VDE-0295.
- Rubber battery cables are largely used in place of functions of heavy duty places and are resistant to abrasion oil and water with quality standards IS-8130, BS-6360, IEC 228 & VDE-0295.
Technical DataTable
PVC Insulated Battery Cables
Cross Section Area (Nom.) | Insulation Thickness (Nom | Overall Diameter (approx.) | Conductor Resistance at 20° C (max.) | Current Carrying Capacity |
Sq.mm | mm | mm | Ohm/Km | Amps |
16 | 1 | 7.8 | 1.21 | 57 |
25 | 1.2 | 9.7 | 0.78 | 71 |
35 | 1.2 | 11 | 0.554 | 91 |
50 | 1.4 | 13.2 | 0.386 | 120 |
70 | 1.4 | 15.3 | 0.272 | 165 |
95 | 1.6 | 17.9 | 0.206 | 200 |
120 | 1.6 | 19.4 | 0.161 | 225 |
150 | 1.8 | 21.9 | 0.129 | 250 |
185 | 2 | 24.5 | 0.106 | 300 |
240 | 2.2 | 28 | 0.801 | 425 |
- Insulation thickness and overall dimensions are nominal values. The number of wires is approximate and strand diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per IS 8130/1984, BS-6360, IEC-228 & VDE-0295.